Group 1 Basic Parameters
Maximum Output Frequency
Settings 50.00~600.00Hz
This parameter determines the AC motor drive's Maximum Output Frequency. All the AC motor
drive frequency command sources (analog inputs 0 to +10V, 4 to 20mA, 0 to 20mAand ±10V) are
scaled to correspond to the output frequency range.
Output Frequency of Motor 1(base frequency and motor rated frequency)
Output Frequency of Motor 2(base frequency and motor rated frequency)
Settings 0.00~600.00Hz
This value should be set according to the rated frequency of the motor as indicated on the motor
nameplate. If the motor is 60Hz, the setting should be 60Hz. If the motor is 50Hz, it should be set
to 50Hz.
Pr.01-35 is used for the application occasion that uses double base motor.
Output Voltage of Motor 1(base frequency and motor rated frequency)
Output Voltage of Motor 2(base frequency and motor rated frequency)
Settings 230V series: 0.0~255.0V
This value should be set according to the rated voltage of the motor as indicated on the motor
nameplate. If the motor is 220V, the setting should be 220.0. If the motor is 200V, it should be set to
200.0.
There are many motor types in the market and the power system for each country is also difference.
The economic and convenience method to solve this problem is to install the AC motor drive. There
is no problem to use with the different voltage and frequency and also can amplify the original
characteristic and life of the motor.
Mid-point Frequency 1 of Motor 1
Settings 0.00~600.00Hz
Mid-point Voltage 1 of Motor 1
Settings 230V series: 0.0~240.0V
Mid-point Frequency 1 of Motor 2
Settings 0.00~600.00Hz
Call 1(800)985-6929 for Sales
deltaacdrives.com
460V series: 0.0~510.0V
460V series: 0.0~480.0V
11-15
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
This parameter can be set during operation.
sales@deltaacdrives.com
Factory Setting: 60.00/50.00
Factory Setting: 60.00/50.00
Factory Setting: 200.0/400.0
Factory Setting: 3.00
Factory Setting: 11.0/22.0
Factory Setting: 3.00
sales@deltaacdrives.com