Settings
The setting of this parameter is in hexadecimal.
This parameter is set via bit setting. If a bit is 1, the corresponding output acts in the opposite way.
Bit setting
bit4
DFM2
DFM1
Terminal Counting Value Attained (return to 0)
Settings 0~65500
The counter trigger can be set by the multi-function terminal MI6 (set Pr.02-06 to 23). Upon
completion of counting, the specified output terminal will be activated (Pr.02-13~02-14, Pr.02-36,
02-37 is set to 18). Pr.02-19 can't be set to 0.
When the display shows c5555, the drive has counted 5,555 times. If display shows c5555•, it
means that real counter value is between 55,550 to 55,559.
Preliminary Counting Value Attained (not return to 0)
Settings 0~65500
When the counter value counts from 1 and reaches this value, the corresponding multi-function
output terminal will be activated, provided one of Pr. 02-13, 02-14, 02-36, 02-37 set to 17
(Preliminary Count Value Setting). This parameter can be used for the end of the counting to make
the drive runs from the low speed to stop.
Di spl ay valu e
[00 -04 =0 1]
TRG
Counter Trigger
( output signal)
P reli min ary Cou nte r V al ue
RY1 P r.0 2- 13=17
Te rmi nal Co unter Valu e
RY 2 P r.0 2-14 =18
Digital Output Gain(DFM 1)
Settings 0~106
It is used to set the signal for the digital output terminals (DFM-DCM) and digital frequency output
(pulse X work period=50%). Output pulse per second = output frequency X Pr.02-21 ≤ 33kHz.
When Pr02-21=0, the external terminal (DFM1) will be multi-function output. Pr02-16 sets up the
function of DFM1's output.
When Pr02-21≥1, the external terminal (DFM1) will be digital frequency output. Output frequency =
H*Gain.
Desired Frequency Attained 1
Call 1(800)985-6929 for Sales
0000h~FFFFh(0:N.O. ; 1:N.C.)
bit3
bit2
bit1
Reserved
RY2
[02-06=23]
02 -13, 02- 14, 0 2-3 6, 02 -37
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
bit0
RY1
02 -20=3
02 -14= 1 7
11-37
deltaacdrives.com
sales@deltaacdrives.com
Factory Setting: 0
Factory Setting: 0
1.0msec
Th e wi dth of trig ger si gnal
02 -19=5
Factory Setting: 1