Delta C200 Series User Manual page 138

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
RUN/STOP
M ulti -fu nctio n outp ut
(mech an ical brake rele as e)
Pr.0 2-11 to 02-14=d1 2
Mechan ical b ra ke
If this parameter is used without DC brake, it will be invalid. Refer to the following operation timing.
RUN/STOP
Multi-function output
(mec hani cal brake
relea se)
Pr.02-11 to 02-14=d12
me chanical brake
Output Current Level Setting for Multi-function Output Terminals
Settings 0~100%
When output current is higher or equal to Pr.02-33, it will activate multi-function output terminal
(Pr.02-13, 02-14, 02-16, and 02-17 is set to 27).
When output current is lower than Pr.02-33, it will activate multi-function output terminal (Pr.02-13,
02-14, 02-16, 02-17 is set to 28).
Call 1(800)985-6929 for Sales
frequ ency
comma nd
07-0 2
DC b ra ke
time du ri ng
s tart-u p
Outp ut
DC b ra ke
freq uen cy
02 -3 2 brak e de lay time
braked
zero
speed
frequency
co mma nd
output
frequency
brake
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
A
B=A
RUN
rele ase
A
B=A
RUN
relea se
11-39
deltaacdrives.com
sales@deltaacdrives.com
07 -0 3
DC bra ke
time du ri ng
stopping
DC b ra ke
STOP
b oun ce time of me ch ani cal brake
braked
Time
ze ro
sp eed
STOP
brak e
Tim e
Factory Setting: 0
sales@deltaacdrives.com