Chapter 10 Summary of Parameter Settings|C200 Series
05 Motor Parameters
Parameter
05-00
Motor Auto Tuning
Full-load Current of
05-01
Induction Motor 1(A)
Rated Power of Induction
05-02
Motor 1(kW)
Rated Speed of Induction
05-03
Motor 1 (rpm)
Pole Number of Induction
05-04
Motor 1
No-load Current of
05-05
Induction Motor 1 (A)
Stator Resistance (Rs) of
05-06
Induction Motor 1
Rotor Resistance (Rr) of
05-07
Induction Motor 1
Magnetizing Inductance
05-08
(Lm) of Induction Motor 1
Stator Inductance (Lx) of
05-09
Induction Motor 1
05-10 ~
Reserved
05-12
Full-load Current of
05-13
Induction Motor 2 (A)
Rated Power of Induction
05-14
Motor 2 (kW)
Rated Speed of Induction
05-15
Motor 2 (rpm)
Pole Number of Induction
05-16
Motor 2
No-load Current of
05-17
Induction Motor 2 (A)
Stator Resistance (Rs) of
05-18
Induction Motor 2
Rotor Resistance (Rr) of
05-19
Induction Motor 2
Magnetizing Inductance
05-20
(Lm) of Induction Motor 2
Stator Inductance (Lx) of
05-21
Induction Motor 2
Induction Motor 1/ 2
05-22
Selection
Frequency for
Y-connection/△-connectio
05-23
n Switch of Induction
Motor
Y-connection/△-connectio
05-24
n Switch of Induction
Motor
Delay Time for
05-25
Y-connection/△-connectio
n Switch of Induction
Call 1(800)985-6929 for Sales
deltaacdrives.com
Explanation
0: No function
1: Rolling test for induction motor(IM) (Rs, Rr, Lm, Lx,
no-load current)
2: Static test for induction motor(IM)
3: No function
4: Rolling test for PM motor magnetic pole
5: Rolling test for PM motor
6: Rolling test for IM motor flux curve
12: FOC Sensorless inertia estimation
13: High frequency and blocked rotor test for PM motor
10~120% of drive's rated current
0~655.35kW
0~65535
1710(60Hz 4poles) ; 1410(50Hz 4 poles)
2~20
0~ Pr.05-01 factory setting
0~65.535mΩ
0~65.535mΩ
0~6553.5mH
0~6553.5mH
10~120%
0~655.35kW
0~65535
1710(60Hz 4 poles) ; 1410(50Hz 4 poles)
2~20
0~ Pr.05-01 factory setting
0~65.535mΩ
0~65.535mΩ
0~6553.5mH
0~6553.5mH
1: motor 1
2: motor 2
0.00~600.00Hz
0: Disable
1: Enable
0.000~60.000 sec.
deltaacdrives.com
Settings
10-16
sales@deltaacdrives.com
Factory
Setting
0
#.##
#.##
1710
4
#.##
0
0
0
0
#.##
#.##
1710
4
#.##
0
0
0
0
1
60.00
0
0.200
sales@deltaacdrives.com