44: Low current output (Pr.06-71 to Pr.06-73)
45: Reserved
46: Master dEb action output
47: Closed brake output
48~49: Reserved
50: Output for CANopen control
51: Output for RS-485
This parameter is used for setting the function of multi-function terminals.
Summary of function settings (Take the normally open contact for example, ON: contact is closed,
OFF: contact is open)
Settings
0
No Function
1
Operation Indication Active when the drive is not at STOP.
Master Frequency
2
Attained
Desired Frequency
3
Attained 1 (Pr.02-22)
Desired Frequency
4
Attained 2 (Pr.02-24)
Zero Speed
5
(frequency
command)
Zero Speed with Stop
6
(frequency
command)
7
Over Torque 1
8
Over Torque 2
9
Drive Ready
Low voltage warn
10
(Lv)
11
Malfunction Indication Active when fault occurs (except Lv stop).
Mechanical Brake
12
Release (Pr.02-32)
13
Overheat
Software Brake
14
Signal Indication
15
PID Feedback Error
16
Slip Error (oSL)
Terminal Count Value
17
Attained (Pr.02-20;
not return to 0)
Preliminary Counter
Value Attained
18
(Pr.02-19; returns to
0)
External Base Block
19
input (B.B.)
20
Warning Output
21
Over-voltage Warning Active when the over-voltage is detected.
Over-current Stall
22
Prevention Warning
Call 1(800)985-6929 for Sales
Functions
Active when the AC motor drive reaches the output frequency setting.
Active when the desired frequency (Pr.02-22) is attained.
Active when the desired frequency (Pr.02-24) is attained.
Active when frequency command =0. (the drive should be at RUN
mode)
Active when frequency command =0 or stop.
Active when detecting over-torque. Refer to Pr.06-07 (over-torque
detection level-OT1) and Pr.06-08 (over-torque detection time-OT1).
Refer to Pr.06-06~06-08.
Active when detecting over-torque. Refer to Pr.06-10 (over-torque
detection level-OT2) and Pr.06-11 (over-torque detection time-OT2).
Refer to Pr.06-09~06-11.
Active when the drive is ON and no abnormality detected.
Active when the DC Bus voltage is too low. (refer to Pr.06-00 low
voltage level)
When drive runs after Pr.02-32, it will be ON. This function should be
used with DC brake and it is recommended to use contact "b"(N.C).
Active when IGBT or heat sink overheats to prevent OH turn off the
drive. (refer to Pr.06-15)
Active when the soft brake function is ON. (refer to Pr.07-00)
Active when the feedback signal is abnormal.
Active when the slip error is detected.
Active when the counter reaches Terminal Counter Value (Pr.02-19).
This contact won't active when Pr.02-20>Pr.02-19.
Active when the counter reaches Preliminary Counter Value
(Pr.02-19).
Active when the output of the AC motor drive is shut off during base
block.
Active when the warning is detected.
Active when the over-current stall prevention is detected.