Delta C200 Series User Manual page 109

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Source of the Master Frequency Command(AUTO)
Settings
It is used to set the source of the master frequency in AUTO mode.
Pr.00-20 and 00-21 are for the settings of frequency source and operation source in AUTO mode.
Pr.00-30 and 00-31 are for the settings of frequency source and operation source in HAND mode.
The AUTO/HAND mode can be switched by the keypad KPC-CC01 or multi-function input terminal
(MI).
The factory setting of frequency source or operation source is for AUTO mode. It will return to
AUTO mode whenever power on again after power off. If there is multi-function input terminal used
to switch AUTO/HAND mode. The highest priority is the mutli-function input terminal. When the
external terminal is OFF, the drive won't receive any operation signal and can't execute JOG.
Source of the Operation Command (AUTO)
Settings 0: Digital keypad
It is used to set the source of the operation frequency in AUTO mode.
When the operation command is controlled by the keypad KPC-CC01, keys RUN, STOP and JOG
(F1) are valid.
Stop Method
Settings 0: Ramp to stop
The parameter determines how the motor is stopped when the AC motor drive receives a valid stop
command.
Call 1(800)985-6929 for Sales
deltaacdrives.com
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
4~5: Reserved
6: CANopen communication card
7: Digital keypad potentiometer
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen communication
1: Coast to stop
11-10
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
sales@deltaacdrives.com
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0
sales@deltaacdrives.com