Air flow rate for cooling
Model No.
VFD004CB21A-20/-21/-21M
VFD007CB21A-20/-21/-21M
VFD015CB21A-20/-21/-21M
VFD022CB21A-20/-21/-21M
VFD004CB23A-20/-21/-21M
VFD007CB23A-20/-21/-21M
VFD015CB23A-20/-21/-21M
VFD022CB23A-20/-21/-21M
VFD037CB23A-20/-21/-21M
VFD007CB43A-20/-21/-21M
VFD015CB43A-20/-21/-21M
VFD022CB43A-20/-21/-21M
VFD037CB43A-20/-21/-21M
VFD040CB43A-20/-21/-21M
VFD055CB43A-20/-21/-21M
VFD075CB43A-20/-21/-21M
The required airflow shown in chart is for installing
single drive in a confined space.
When installing the multiple drives, the required air
volume should be the required air volume for single
drive X the number of the drives.
Call 1(800)985-6929 for Sales
deltaacdrives.com
NOT E
The mounting clearances stated in the figure is for installing the drive in an
open area. To install the drive in a confined space (such as cabinet or
electric box), please follow the following three rules: (1) Keep the minimum
mounting clearances. (2) Install a ventilation equipment or an air
conditioner to keep surrounding temperature lower than operation
temperature. (3) Refer to parameter setting and set up Pr. 00-16, Pr.00-17,
and Pr. 06-55.
The following table shows the heat dissipation and the required air
volume when installing a single drive in a confined space. When
installing multiple drives, the required air volume shall be multiplied
by the number the drives.
Refer to the chart (Air flow rate for cooling) for ventilation equipment
design and selection.
Refer to the chart (Power dissipation) for air conditioner design and
selection.
Flow Rate
Flow Rate
3
(cfm)
(m
/hr)
-
-
-
-
15
26
15
26
-
-
-
-
15
26
15
26
15
26
-
-
-
-
15
26
15
26
15
26
15
26
24
41
2-3
deltaacdrives.com
Chapter 2 Installation|C200 Series
Power dissipation of AC motor drive
Power Dissipation
Loss External
Internal
(Heat sink)
16
20
32
39
60
52
85
69
21
17
35
26
56
32
82
34
118
43
35
24
47
27
75
30
110
33
126
34
145
37
212
83
The heat dissipation shown in the chart is
for installing single drive in a confined
space.
When installing the multiple drives,
volume of heat dissipation should be the
heat dissipated for single drive X the
number of the drives.
Heat dissipation for each model is
calculated by rated voltage, current and
default carrier.