Settings 0.00~600.00Hz
Dwell Time at Decel.
Settings 0.00~600.00 sec
Dwell Frequency at Decel.
Settings 0.00~600.00 Hz
In the heavy load situation, Dwell can make stable output frequency temporarily, such as crane or
elevator.
Pr.07-15 to Pr.07-18 is for heavy load to prevent OV or OC occurs.
Fan Cooling Control
Settings 0: Fan always ON
This parameter is used for the fan control.
Setting 0: Fan will be ON as the drive's power is turned ON.
Setting 1: 1 minute after AC motor drive stops, fan will be OFF
Setting 2: AC motor drive runs and fan will be ON. AC motor drive stops and fan will be OFF.
Setting 3: Fan run according to IGBT and capacitance temperature. Fan will be ON when
preliminary capacitance temperature is higher than 60oC. Fan will be OFF, when capacitance
temperature is lower than 40oC.
Setting 4: Fan is always OFF
Emergency Stop (EF) & Force Stop
Settings
Call 1(800)985-6929 for Sales
deltaacdrives.com
Frequency
07-16
Dwell
Frequency
07-15
at Accel.
Dwell Time
at Accel.
1: 1 minute after the AC motor drive stops, fan will be OFF
2: When the AC motor drive runs, the fan is ON. When the AC motor drive
stops, the fan is OFF
3: Fan turns ON when preliminary heat sink temperature (around 60
attained.
4: Fan always OFF
0: Coast to stop
st
1: Stop by 1
deceleration time
nd
2: Stop by 2
deceleration time
rd
3: Stop by 3
deceleration time
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
07-17
Dwell Time
at Decel.
Dwell at accel./decel.
11-106
sales@deltaacdrives.com
Factory Setting: 0.00
Factory Setting: 0.00
07-18
Dwell
Frequency
at Decel.
Time
Factory Setting: 0
o
C) is
Factory Setting: 0
sales@deltaacdrives.com