7.3

Setting an IP Address

In the controller's initial state, the following IP addresses are active for the
ETHERNET interface (Port X1 and Port X2):

Table 35: Default IP Addresses for ETHERNET Interfaces

ETHERNET Interface
X1
X2
Adapt IP addressing to your specific system structure to ensure that the PC and
the controller can communicate with one another using one of the available
configuration tools (WBM, WAGO ETHERNET Settings or CBM – see section
"Configuration").
Example for incorporating the controller (192.168.2.17) into an existing
network:
The IP address of the host PC is 192.168.1.2.
The controller and host PC must be in the same subnet (regardless of the
IP address of the host PC).
With a subnet mast of 255.255.255.0, the first three digits of the IP address
of the host PC and controller must match so that they are located in the
same subnet.

Table 36: Network Mask 255.255.255.0

Host PC
192.168.1.2
Default Setting
Dynamic assignment of IP address using DHCP
("Dynamic Host Configuration Protocol")
Static assignment of IP addresses:
-
IP address: 192.168.2.17
-
Network mask: 255.255.255.0
Subnet Address Range for the Controller
192.168.1.1 or 192.168.1.3 ... 192.168.1.254
Version 1.2.0, valid from FW Version 03.02.02(14)