Mounting
5.3.2

WAGO DIN Rails

WAGO carrier rails meet the electrical and mechanical requirements shown in the
table below.

Table 34: WAGO DIN Rails

Item No.
210-112
210-113
210-197
210-114
210-118
210-198
210-196
Observe the mounting distance of the DIN rail when the load is increased!
With increased vibration and shock load, mount the DIN rail at a mounting
distance of max. 60 mm.
5.4

Spacing

The spacing between adjacent components, cable conduits, casing and frame
sides must be maintained for the complete fieldbus node.

Figure 21: Spacing

The spacing creates room for heat transfer, installation or wiring. The spacing to
cable conduits also prevents conducted electromagnetic interferences from
influencing the operation.
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
Description
35 × 7.5; 1 mm; steel; bluish, tinned, chromed; slotted
35 × 7.5; 1 mm; steel; bluish, tinned, chromed; unslotted
35 × 15; 1.5 mm; steel; bluish, tinned, chromed; slotted
35 × 15; 1.5 mm; steel; bluish, tinned, chromed; unslotted
35 × 15; 2.3 mm; steel; bluish, tinned, chromed; unslotted
35 × 15; 2.3 mm; copper; unslotted
35 × 8.2; 1.6 mm; aluminum; unslotted
WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB