Figure 100: Text Detail - Marking Example For Approved Ex I I/O Modules; Table 227: Description Of Marking Example For Approved Ex I I/O Modules - WAGO 750-8215 Manual

I/o-system 750
Table of Contents

Advertisement

326 Use in Hazardous Environments
Figure 100: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Table 227: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Marking
Dust
Ex
nA
[ia IIIC]
IIC
T4
Gc
X
Gases
Ex
nA
[ia Ga]
IIC
T4
Gc
X
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
750-8215 PFC200; G2; 4ETH CAN USB
Description
Explosion protection mark
Type of protection
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
Group
Temperature class
Equipment protection level (EPL)
Symbol used to denote specific conditions of use
Explosion protection mark
Type of protection
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 0
Group
Temperature class
Equipment protection level (EPL)
Symbol used to denote specific conditions of use