114 Commissioning

7.8.1.8.2 "Default Gateway n" Groups

You can configure two default gateways. The controller transmits all network data
not going to a station on the local network to a default gateway. First the gateway
with the lowest metric is addressed. If this is not reached, the second gateway is
used. The selection is random if the metric is the same.
A default gateway can also be configured via DHCP. These default gateways are
given the metric 10, by which they are normally used before the static gateways.
Table 47: WBM "TCP/IP Configuration" Page – "Default Gateway n" Group
Parameters
Gateway enabled
Destination Address
Destination Mask
Gateway Address
Gateway Metric
Click [Submit] to apply the change. The change is effective immediately.
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
750-8215 PFC200; G2; 4ETH CAN USB
Explanation
Set here whether the selected default gateway is to
be used.
Disabled
The default gateway is not used.
Enabled
The default gateway is used.
Enter here if any network devices or only a specific
network device or device pool is to be accessed.
"default"
Any network devices can be reached.
Only a specific network device or
Network
device from the set address pool can
address
be reached.
Enter the subnet mask of the station.
If "default" is entered at Destination Address, the
value "0.0.0.0" must be entered here.
Enter the address of the default gateway.
Set here a number as the metric. With multiple
default gateways, the metric defines the gateway to
which data packets are first sent. Priority is given to
the gateway with the lower metric. The default value
for the metric is 20.
The lowest value is 0.
The highest value is 4.294.967.295.
WAGO-I/O-SYSTEM 750