354 Appendix
Table 266: SSI Transmitter Interface Modules
Input Process Image
Offset
0
1
750-630/000-004, -005, -007
In the input process image, SSI transmitter interface modules with status occupy
5 usable bytes, 4 data bytes, and 1 additional status byte. A total of 3 words are
assigned in the process image via word alignment.
Table 267: SSI Transmitter Interface I/O Modules with an Alternative Data Format (/000-004, -005, -
007)
Input Process Image
Offset
0
1
2
17.1.5.8
Incremental Encoder Interface Modules
Incremental Encoder Interface Modules
750-631/000-004, -010, -011
The above Incremental Encoder Interface modules have 5 bytes of input data
and 3 bytes of output data. The following tables illustrate the Input and Output
Process Image, which have 4 words into each image. Word alignment is applied.
Table 268: Incremental Encoder Interface Modules 750-631/000-004, --010, -011
Input Process Image
Offset
0
1
2
3
Output Process Image
Offset
0
1
2
3
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
Byte Designation
High Byte
D1
D3
Byte Destination
High Byte
-
D1
D3
Byte Designation
High Byte
-
D1
-
D4
Byte Designation
High Byte
-
D1
-
-
WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
Low Byte
D0
D2
High Byte
S
not used
D0
D2
Low Byte
S
not used
D0
-
D3
Low Byte
C
not used
D0
-
-
Description
Data bytes
Description
Status byte
Data bytes
Description
Status byte
Counter word
not used
Latch word
Description
Control byte
Counter setting word
not used
not used