Analog Output Modules; Channel Analog Output Modules; Table 255: 2 Channel Analog Output Modules; Table 256: 4 Channel Analog Output Modules - WAGO 750-8215 Manual

I/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
17.1.4

Analog Output Modules

The analog output modules provide 16-bit output values and 8 control/status bits
per channel.
The controller only uses the 8 control/status bits internally for
configuration/parameterization (e.g., via WAGO-I/O-CHECK).
Therefore, only the 16-bit measurement values for each channel are in Intel
format and are mapped by word in the output process image for the controller.
When digital output modules are also present in the node, the analog output data
is always mapped into the Output Process Image in front of the digital data.
Information on the structure of control and status bytes
For detailed information on the structure of a particular I/O module's
control/status bytes, please refer to that module's manual. Manuals for each
module can be found on the Internet at www.wago.com.
17.1.4.1

2 Channel Analog Output Modules

750-550, -552, -554, -556, -560, -562, 563, -585, -586, (and all variations),
753-550, -552, -554, -556

Table 255: 2 Channel Analog Output Modules

Output Process Image
Offset
0
1
17.1.4.2
4 Channel Analog Output Modules
750-553, -555, -557, -559,
753-553, -555, -557, -559

Table 256: 4 Channel Analog Output Modules

Output Process Image
Offset
0
1
2
3
Byte Destination
High Byte
D1
D3
Byte Destination
High Byte
D1
D3
D5
D7
Version 1.2.0, valid from FW Version 03.02.02(14)
Low Byte
D0
Output Value Channel 1
D2
Output Value Channel 2
Low Byte
D0
Output Value Channel 1
D2
Output Value Channel 2
D4
Output Value Channel 3
D6
Output Value Channel 4
Appendix 347