WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
The BF LED indicates following diagnostics:
Table 208: "BF" Diagnostics LED
Status
Green
Green, flashing,
500 ms
Red
Red, flashing,
500 ms
Off
Explanation
PROFINET
communication
established
PROFINET DCP
signal request
received;
Signaling duration: 3
seconds
PROFINET
configured; no
PROFINET-compliant
link available.
PROFINET
configured; link
available; no
connection to the
PROFINET IO
Controller.
No PROFINET device
configuration was
created in
e!COCKPIT. No
PROFINET
communication
possible.
Version 1.2.0, valid from FW Version 03.02.02(14)
Remedy
---
---
Check the network connection to the
PROFINET IO Controller.
Check the network connection to the
PROFINET IO Controller.
Check the device configuration in
e!COCKPIT or create the device
configuration.
Diagnostics 297
Manual