Register 0xFA03 – Watchdog Config
9.2.1.4
This register contains the configuration parameters for the watchdog. The
register is organized in bits, see following table.
The register can be read and written irrespective of the watchdog state in the
SIMPLE_WATCHDOG operation mode.
However, in the ADVANCED_WATCHDOG operation mode, the register can only
be read and written in the WATCHDOG_UNCONFIGURED and
WATCHDOG_STOPPED states.
If the watchdog is active (WATCHDOG_RUNNING or WATCHDOG_EXPIRED
state), only a read access is permissible. The response to a write request in this
case is an ILLEGAL_FUNCTION (0x01) exception.

Table 182: Watchdog Configuration

Bit Name/Bit Identifier
0 EXPLICIT_
TRIGGER_ONLY
1 TRIGGER_ON_
STATUS_REG
2 CLOSE_ALL_TCP_
CONNECTIONS
7 SELECT_
ADVANCED_
SIMPLE_MODE
*Default setting
The individual options are activated if the relevant bit or bit combination is set.
Explanation
Activates the Explicit Trigger mode
0* All valid Modbus requests are considered as
watchdog triggers. Access to register 0xFA02
(Watchdog Status) is the only exception.
1 Only the writing of register 0xFA00 (Watchdog
Command) with the value 0x5555
(WATCHDOG_START) is considered as the
watchdog trigger. The exception is also here the
access to the register 0xFA02 (Watchdog
Status).
Activates the watchdog trigger by (read)
access to register 0xFA02 (Watchdog Status)
0* The reading of the watchdog status is not
considered as a watchdog trigger.
1 The reading of the watchdog status triggers the
watchdog.
Activates the closing of all Modbus TCP connections
with the expiry of the timeout (transition to
WATCHDOG_EXPIRED state)
0 Existing Modbus TCP connections remain open.
1* All existing Modbus TCP connections are closed.
Determines the watchdog operation mode
0* Advanced Mode: The watchdog must be
controlled explicitly via commands (see register
0xFA00 Watchdog Command).
1 Simple Mode: The watchdog is activated directly
with a timeout > 0 in register 0xFA01 (Watchdog
Timeout). Each trigger restarts the running as
well as the expired watchdog. The watchdog can
only be stopped by switching to Advanced mode.
Version 1.2.0, valid from FW Version 03.02.02(14)
Modbus – e!RUNTIME 233
Manual

Advertisement