Modbus Registers; Table 179: Wago Modbus Registers - WAGO 750-8215 Manual

I/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
9.2

Modbus Registers

Table 179: WAGO Modbus Registers

Modbus Address
Dec.
Watchdog Configuration Registers
64,000
64,001
64,002
64,003
64,004
Status Registers
64,010
64,011
64,012
64,013
Electronic Type Label
64,016
64,020
64,021
64,022
Process Image Version
64,023
Network Configuration
64,032
Process Image Registers
64,064
64,065
64,066
64,067
64,068
64,069
Data Length
in Words
Hex.
0xFA00
1
0xFA01
1
0xFA02
1
0xFA03
1
0xFA04
1
0xFA0A
1
0xFA0B
1
0xFA0C
1
0xFA0D
1
0xFA10
4
0xFA14
1
0xFA15
1
0xFA16
1
0xFA17
1
0xFA20
3
0xFA40
1
0xFA41
1
0xFA42
1
0xFA43
1
0xFA44
1
0xFA45
1
Version 1.2.0, valid from FW Version 03.02.02(14)
Modbus – e!RUNTIME 227
Access Description
w
Watchdog command register
rw
Watchdog timeout register
ro
Watchdog status register
rw
Watchdog config register
Modbus TCP connection
rw
watchdog register
LED flash code I/O-LED
ro
(sequence 1 of 3)
LED flash code I/O-LED
ro
(sequence 2 of 3)
LED flash code I/O-LED
ro
(sequence 3 of 3)
ro
PLC State : 1 = Stop; 2 = Run
Order number, e.g.,
ro
0750810100400001
ro
Firmware status
ro
Hardware version
ro
Firmware loader
Version of the Modbus process
ro
image
ro
MAC-ID 1
Number of input registers, analog
ro
and digital (total size of the
Modbus IN space) 0x7D00
Number of input registers, analog
ro
0x7D00
Number of input registers, digital
ro
0x8000
Number of output registers,
ro
analog and digital (total size of
the Modbus OUT space) 0x7D00
Number of output registers,
ro
analog 0x7D00
Number of output registers,
ro
digital 0x8000