WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
11.2
Configuration and Parameterization with
e!COCKPIT
The PROFINET parameters are set in e!COCKPIT with the configurator
described below.
11.2.1

PROFINET Data Point Configurator

When configuring the PROFINET IO device (e.g., 750-8215), modules and data
points are created that are used for communication between PROFINET IO
devices and PROFINET IO controllers. The PROFINET IO controller can be an
external device that is not configured in e!COCKPIT.
The configuration is done in the "PROFINET I-Device" tab in the Device Detail
view. The following functions can be executed:
Creation/deletion of PROFINET modules and contained data points
Mapping of data points of existing application variables (CODESYS
configuration user interface)
Creation of data points as new CODESYS variables (CODESYS
configuration user interface); these can be addressed directly in the
program editor.
Export of the configuration in the form of a device description file (XML file
in GSDML format)
Modules with defined data points are listed, added or deleted in the "PROFINET
I-Device" tab. Module/data points are shown in tabular form. Each column
represents a property of the data point. After a data point is created, properties
(interdependent) can be changed. The individual table cells serve as entry or
selection windows.
As support for configuring the input/output data areas of the PROFINET I-Device,
the respective data direction, as well as used and maximum available user data
are listed at the bottom of the configurator. The size of the user data and the user
data qualifier defined in the PROFINET protocol are included in the calculation.
Version 1.2.0, valid from FW Version 03.02.02(14)
PROFINET 287
Manual