166 Commissioning
"Advanced Intrusion Detection Environment (AIDE) Page"
7.8.1.38
The network security settings are available on the "Advanced Intrusion Detection
Environment (AIDE)" page.
7.8.1.38.1 "Run AIDE check at startup" Group
Table 109: "Advanced Intrusion Detection Environment (AIDE) WBM page" – "Run AIDE check at
startup" Group
Parameter
Service active
Click the [Submit] button to apply the changes. The changes only take effect
when the controller restarts.
7.8.1.38.2 "Control AIDE and show log" Group
Table 110: "Advanced Intrusion Detection Environment (AIDE)" WBM page – "Control AIDE and
show log" Group
Parameter
Select Action
Read all notifications
Read only the last n
Automatic refresh cycle
(sec)
To refresh the display or to enable cyclic refresh, click the [Refresh] button. The
button is only visible if cyclic refresh is enabled and has not yet started.
To stop cyclic refresh again, click the [Stop] button. The button is only visible if
cyclic refresh is enabled.
The cyclical update is performed for as long as the "Advanced Intrusion Detection
Environment (AIDE)" page is opened. If you change the WBM page, the update
is stopped until you call up the "Advanced Intrusion Detection Environment
(AIDE)" page again.
Manual
Version 1.2.0, valid from FW Version 03.02.02(14)
750-8215 PFC200; G2; 4ETH CAN USB
Explanation
Here, you can activate/deactivate the "AIDE check"
when the controller is started.
Explanation
Select here the action to be executed.
readlog
The log data are displayed.
The database is initialized and filled with
init
the current values.
The current values are compared against
check
the values stored in the database.
The current values are compared with the
update
values stored in the database and the
database then updated.
Activate display of all messages.
Activate display of only the last n messages. You
also specify the number of messages to be
displayed.
Select the check box to enable cyclic refresh.
Enter the cycle time in seconds in which a cyclic
refresh is performed. The label of the button
("Refresh"/"Stop") changes depending on status.