WAGO-I/O-SYSTEM 750
750-8215 PFC200; G2; 4ETH CAN USB
9.2.2

Status Registers

9.2.2.1

PLC Status Register

The register 0xFA0D supplies the current status of the controller.
Possible values:
1 = PLC Stop - PLC is in STOP status.
2 = PLC Run - PLC is in RUN status
9.2.3

Electronic Nameplate

Registers 0xFA10–0xFA17 contain information from the electronic nameplate. It
is possible to read the entire nameplate or a consecutive portion of it all at once.
9.2.3.1

Order Number

The registers 0xFA10–0xFA13 contain the WAGO order number of the controller.
Example: 0750-8202/0025-0001.
0xFA10 = 0750,
0xFA11 = 8202,
0xFA12 = 0025,
0xFA13 = 0001
9.2.3.2

Firmware Version

The register 0xFA14 contains the firmware version of the controller.
9.2.3.3

Hardware Version

The register 0xFA15 contains the hardware version of the controller.
9.2.3.4

Firmware Loader/Boot Loader

The register 0xFA16 contains the firmware loader/boot loader version of the
controller.
9.2.4

Modbus Process Image Version

The register 0xFA17 contains the Modbus process image version of the
controller.
9.2.5

Modbus Process Image Registers

The registers 0xFA40–0xFA45 contain size information for the process image
spaces of the controller for bit and register accesses.
Version 1.2.0, valid from FW Version 03.02.02(14)
Modbus – e!RUNTIME 235
Manual