5.2 Setting Communications Parameters (IP Address
Settings)
Prerequisites
You have logged in to the system as admin.
Procedure
Step 1 On the main screen, choose Settings > Comm Settings > IP Settings.
Step 2 Set IP assigning mode to DHCP Automatic.
----End
5.3 Setting Temperature and Humidity Values and
(Optional) Enabling T/H Sensors
Prerequisites
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H sensor.
displayed.
Issue 06 (2020-03-20)
Parameter
If IP assigning mode is set to DHCP Automatic, the values of IP address, Subnet mask, and Gateway
are automatically assigned.
The T/H sensors outside the cabinet need to be enabled when they are installed,
otherwise, skip
Step
2.
If you need to enable a humidity and temperature sensor, log in as the admin user.
This section describes how to enable Cold aisle sensor 1.