Huawei RH8100 V3 User Manual page 100

Table of Contents

Advertisement

RH8100 V3 Server
User Guide
Data
No data preparation is required for this operation.
Tools
Hardware
A ground cable has OT terminals at both ends and its cross-sectional area is 25
mm² (0.04 in.²), as shown in
Figure 3-9 Ground cable
Procedure
Step 1 Wear an ESD wrist strap or ESD gloves.
Step 2 Use a Phillips screwdriver to loosen the screw in the ground point on the rear of
the server, and connect one end of the ground cable to the removed screw. Install
the screw in the ground point, and tighten the screw.
Issue 30 (2019-12-19)
The server and its internal components are properly installed.
Ground cables are available and placed near the server.
Phillips screwdriver: used to tighten screws.
ESD wrist strap or ESD gloves: used to prevent ESD damage.
● The devices in a cabinet, such as the power distribution box (PDB) and chassis, use the
same type of ground cables.
● The resistance between the chassis and the earth must be less than 5 ohms.
Copyright © Huawei Technologies Co., Ltd.
Figure
3-9.
3 Installing the RH8100 V3
90