Adding New Carriers and EPN Cabinets

DEFINITY AUDIX Power Procedures

Power Down the AUDIX System
A yellow caution sticker on the system's power unit notifies technicians to shut
down the DEFINITY AUDIX System prior to powering down the system.
1. Log into the AUDIX System as craft.
2. Type reset system shutdown and press
3. Press
4. The SHUTDOWN Completed message appears when the AUDIX is
successfully shut down. This takes about 2 minutes.
5. You can now shut down the carrier or remove the AUDIX System for
service.
!
CAUTION:
If leaving AUDIX System in the carrier, back it out about 2 in. (5 cm) to
eliminate the possibility of damage due to power surges.
Power Up the AUDIX System
If the AUDIX was removed from the cabinet:
1. Re-install the AUDIX and allow it to power up automatically.
2. Check for AUDIX System errors.
If the AUDIX remained in the cabinet but the cabinet was powered down:
1. Reseat the AUDIX
2. Power up the cabinet. The AUDIX reboots automatically.
3. Check for AUDIX System errors.
If the AUDIX remained in the cabinet and the cabinet was not powered
down:
1. At the AUDIX console, hold the
2. Enter 5 at the prompt. In about 2 minutes, the AUDIX boots up.
3. When the system initialization is complete, log in as craft.
4. Check for AUDIX System errors.
6-94
Issue 7 November 2003
again to start the shutdown process.
Enter
.
Enter
key and enter cc.
crtl
555-233-115