Modbus Communication
4.2 Software Programming
Example
The following example shows how the network can be programmed to trip the input medium
voltage:
• The PLC writes to register 'Data to Drive 03' which is programmed to 'Net Input Flag 1' using
the procedure described in the previous paragraphs.
• The SOP sets a flag bit that uses a digital output to trip input medium voltage, using the
following SOP source code:
;ExternalDigitalOutput01h_O Use digital output to trip input
medium voltage
ExternalDigitalOutput01h_O = Network1FixedRegBit9_I;
• The PLC writes the contents of 'Net Input Flag 1', bit 9 (Network1Flag9_I) to create an input
medium voltage trip.
4.2.2

Programmable Outputs from the Drive

Description
There are 64 output bits available for user programming through the SOP file. These bits can be
programmed to set or reset any other bits used within the SOP.
Programming Procedure
1. Locate the first data from drive register that is programmable using Table Correspondence
between Drive Parameter ID and Communication Protocol Address in Section Parameter
Assignment/Addressing.
You will see that the first programmable data from drive register for network 1 is register 'Data
from Drive 03', which corresponds to parameter ID (9403).
2. Enter parameter ID (9403).
3. The pick list of data from drive variables will appear. Refer to Table Data from Drive Pick List
Variables in Section Parameter Assignment/Addressing for a list of data from drive pick list
variables.
4. Scroll through the pick list until you come to 'Net1 Out Reg 1' and press [ENTER]. This setting
uses the first 16 bits of the possible 64 bits.
5. Select 'Net1 Out Reg 2' to use the second set of 16 bits, and so on.
The pick list variables and the corresponding programmable output bits are found in the
following tables for network 1 and 2, respectively.
Table 4-7
Pick list variable in 'Data from Drive Reg nn' me‐
nus
Net1 Out Reg 1
Net1 Out Reg 2
28
Network 1: Programmable output bits (parameter ID 9403-9464)
Related Drctry.plus bits
Network1Flag0_O ~ Network1Flag15_O
Network1Flag16_O ~ Network1Flag31_O