Offline commissioning

When you set the safety function parameters offline, you have to download them to the
inverter. Once you have downloaded them, you have to finish commissioning the safety
functions online.
The screens for the safety functions differ from each other slightly depending on whether you
work with STARTER online or offline. Follow the descriptions in this manual in order to set all
of the necessary parameters in line with the requirements of your application (this also
applies when setting the parameters offline).
4.7.1

Offline parameterization

● Call up the safety functions in STARTER.
● Select the checkbox at the bottom of the dialog to copy the parameters:
● Set the safety function parameters offline.
● Once you have finished setting the parameters, save your project by clicking the
4.7.2

Downloading parameters

● Go online with STARTER and start downloading the parameters to the inverter. To do so,
● Call the safety functions screen form
● Click on the "Change settings" button
● Click on the "Activate settings" button
● Save your settings (copy RAM to ROM).
● Switch off the inverter supply voltage.
● Wait until all LEDs on the inverter go dark. Now switch on the inverter supply voltage
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB
Follow the descriptions in this manual starting with the section Selecting the
commissioning method (Page 108).
button.
click the
button.
again. Your settings only become effective after this power-on reset.