Connecting-up
3.1

Power connections

♦ The unit will be destroyed if the input- and output terminals are interchanged!
♦ The converter will be destroyed if the DC link terminals are interchanged or short-
♦ The coils of contacts and relays which are connected to the same supply as the
♦ It is not permisible that the converter is connected-up through an e.l.c.b. (ground fault
The converters should be fused on the line side with fuses according to Table 0.1. In order to reduce noise and
to limit the harmonics fed back into the supply a 2% commutating reactor should be used to connect the
converter to the supply. Refer to Table 3.1 for the Order Nos. for the fuses and the line commutating reactors.
To maintain the radio interference suppression regulations, refer to the Instruction Manual, Part 2, Section
„Measures to maintain the radio interference suppression regulations".
The position of the connecting terminals can be seen in the dimension drawings (+ Section 2.4).
Line connection:
Motor connection:

Protective conductor connection:

Connections must be established using cable lugs with bolts according to Table 3.2.
Converters type of construction H: The busbars of the motor connection are rotated through 90 °.
Due to the 230 V fan a transformer is integrated into the converters. The terminals on the primary side must be
connected corresponding to the rated input voltage.
Depending on the motor insulation strength and the length of the motor feeder cable, it may be necessary to
install one of the following options between the motor and the converter:
♦ Output reactor
♦ dv/dt-filter
♦ Sinusoidal filter
Information regarding selection and dimensioning is provided in Section „Options".
3-2
circuited!
converter or are located in the vicinity of the converter, must be provided with
overvoltage limiters, e.g. RC elements.
circuit interrupter) (DIN VDE 0160).
U1/L1
V1/L2
U2/T1
V2/T2
PE1
PE2
NOTE FC and VC
only for FC and VC, not permissible for SC
only for FC and VC, not permissible for SC
WARNING
W1/L3
W2/T3
NOTE
SIMOVERT MASTER DRIVES
08.96