Further notes on operation

6.3 Interface in the user program

6.3
Interface in the user program
Status displays with the program block AG_SEND
For the CP 342-5 (6GK7 342-5DA03-0XE0), note the following over and above the
information in /4/ (Page 48), Release 03/2010:
DONE
ERROR
0
1
Status displays with the program block DP_DIAG
For the CP 342-5 (6GK7 342-5DA03-0XE0), note the following over and above the
information in /4/ (Page 48), Release 03/2010:
DONE
ERROR
STATUS
1
0
0000
1
0
8248
6.4

Other information available about the CP

FAQs on the Internet
You will find detailed information (FAQs) on using the PROFIBUS S7-CPs at the following
Internet address (entry type: FAQ):
10805945 (http://support.automation.siemens.com/WW/view/en/10805945)
34
STATUS
Meaning
8315
Possible additional meaning:
H
This error code can also occur with bus problems (for example physical
disturbances due to bad cable connections or different settings for the transmission
speed on the nodes).
Possible
Meaning
with DTYPE
0, 1
Job completed without error
H
and 4-9
Note:
With DTYPE 2, 3 and 10, error-free execution is indicated by a status
code other than "0". Below (see table DP_DIAG codes in /4/ (Page 48)),
you will see the detailed status codes for error-free execution for the
range:
82XX
If an error occurs in execution, you receive status codes in the following
ranges:
80XX
2, 3, 10
Job completed without error
H
Note: This is the default code for the named diagnostics types if there is
no special situation to signal.
H
, 83XX
, 8FXX
H
H
H
CP 342-5 / CP 342-5 FO
Manual, 10/2011, C79000-G8976-C146-09