vacon • 206
Bit
10
11
12
13
14
15
1) This functionality can be enabled/disabled by application from drive parameters.
11
Function
0
Jogging 1
1
0
Jogging 2
1
0
Quick stop
1
0
Reserved
1
0
Reserved
1
0
1)
Master connected
1
Table 207. FBFixedControlWord modifications in VACON
Bit
Function
3
Fieldbus DIN1
4
Fieldbus DIN2
5
Fieldbus DIN3
6
Fieldbus DIN4
7
Fieldbus DIN5
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
APPENDIX 1 - VACON® IO DATA DESCRIPTION
Description
No action.
Jogging request with jogging reference 1.
No action.
Jogging request with jogging reference 2.
No action.
Drive executes quick stop / emergency stop.
-
-
-
-
Only in NXP. Fieldbus sets this bit to zero when it
detects that there is no connection to master.
Only in NXP. Fieldbus sets this bit to one when it
detects valid connection from the master.
Description
0
Fieldbus DIN 1 off
1
Fieldbus DIN 1 on
0
Fieldbus DIN 2 off
1
Fieldbus DIN 2 on
0
Fieldbus DIN 3 off
1
Fieldbus DIN 3 on
0
Fieldbus DIN 4 off
1
Fieldbus DIN 4 on
0
Fieldbus DIN 5 off
1
Fieldbus DIN 5 on
®
NXP