Vacon optea Installation Manual page 130

Advanced/dual port ethernet board
Hide thumbs Also See for optea:
Table of Contents

Advertisement

vacon • 130
Attribute
No. of elements
Parameter Number
Subindex
Attribute
No. of elements
Parameter Number
Subindex
Parameter datatype
Number of parameters
Value
Parameter datatype
Number of parameters
Value
The following table contains messages sent during writing values to ID 103 and ID 104.
Message
1
Write request
2
Write request response from AC drive to PLC
-
PLC waits until AC drive has finished processing the requested operation
3
PLC sends read request
Read request
4
response
Answer indicates a successful operation.
8
Table 98. Request to write the value of parameter ID 103 and ID 104
Field
Table 99. Messages sent and received during writing value to ID 103
Operation
Request header
Parameter address
Parameter value
Response header
Contents
0x10 = Value
0x01
0x2711 (10001d)
0x0067 (103d, ID 103)
0x10 = Value
0x01
0x2711 (10001d)
0x0068 (104d, ID 104)
0x42 = WORD
0x01
0x0028 (Value for ID 103)
0x42 = WORD
0x01
0x0028 (Value for ID 104)
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
PROFINET IO
Data
0x06 0x02 0x01 0x02
0x10 0x01 0x27 0x11 0x00 0x67
0x10 0x01 0x27 0x11 0x00 0x68
0x42 0x01 0x00 0x28
0x42 0x01 0x00 0x28
0x06 0x02 0x01 0x01