PROFINET IO
vacon • 107
Bit 2: State of operation
This bit indicates whether the drive is operating or not. When the bit has the value 0, the drive is not
operating. When the bit has the value 1, the drive is operating.
Bit 3: Presence of fault
This bit indicates the presence of unacknowledged faults in the drive. When the bit has the value 0,
no unacknowledged faults are present in the drive. When the bit has the value 1, at least one
unacknowledged fault is present in the drive.
Bit 4: Coast stop activated
This bit indicates whether a coast stop command is active or not. When the bit has the value 0, a
coast stop command is active. When the bit has the value 1, no coast stop command is active.
Bit 5: Quick stop activated
This bit indicates whether a quick stop command is active or not. When the bit has the value 0, a
quick stop command is active. When the bit has the value 1, no quick stop command is active.
Bit 6: Switching on inhibition
This bit indicates whether the power electronics may be switched on or not. When the bit has the
value 0, the power electronics may be switched on. When the bit has the value 1, the power
electronics are prevented from switching on.
Bit 7: Presence of warning
This bit indicates the presence of warning/alarm information in the drive. When the bit has the value
0, no warning is present. When the bit has the value 1, a warning is present.
Bit 8: Running at setpoint
This bit indicates whether the drive is operating and the actual speed value matches the setpoint
value. When the bit has the value 0, the actual speed value does not match the setpoint value. When
the bit has the value 1, the actual speed value matches the setpoint value.
Bit 9: Request control by master
This bit indicates whether the fieldbus master should take control of the drive. When this bit has the
value 0, the master does not take control of the drive. When this bit has the value 1, the master is
requested to take control of the drive.
In OPTE9, this bit depends on the configuration for the drive control place. If the control place is
assigned to fieldbus, the bit has the value 1. If the control place is elsewhere, the bit has the value 0.
Bit 10: Setpoint reached or exceeded
This bit indicates whether the setpoint value has been reached or exceeded. When this bit has the
value 0, the setpoint value has not been reached or exceeded. When this bit has the value 1, the
setpoint value has been reached or exceeded.
Bit 12: Drive running
This bit indicates drive state. If bit is 1, the motor is running. If bit is zero, the motor has been
stopped.
Bit 13: Drive ready
This bit indicates drive state. If bit is 1, the drive is ready for transition to running state.