vacon • 198
9.3.3.2
Start/Stop bit in VACON
If one of the "RunFwd" or "RunRev" bits in an Output Assembly has the value 1, the "Start/Stop" bit
®
0 in the VACON
If both the "RunFwd" and "RunRev" bits have the value 1, no changes are done to
FBFixedControlWord.
9.3.3.3
Direction bit in VACON
If the "RunRev" bit in an Output Assembly has the value 1, and the "RunFwd" bit in the assembly has
the value 0, then the "Direction" bit 1 in the VACON
bit is set to 0.
9.3.3.4
Fault Reset bit in VACON
The "Fault Reset" bit in an Output Assembly is mapped to the "Fault Reset" bit 2 in the VACON
FBFixedControlWord. Both bits are rising-edge sensitive.
9.3.3.5
Request Fieldbus Control bit in VACON
The "NetCtrl" bit in an Output Assembly is not mapped to the "Request Fieldbus Control" bit 8 in the
®
VACON
FBFixedControlWord because this way you can place the drive to the IO or keypad control
while fieldbus is active.
9.3.3.6
Request Fieldbus Reference bit in VACON
The "NetRef" bit in an Output Assembly is not mapped to the "Request Fieldbus Reference" bit 9 in
®
the VACON
FBFixedControlWord.
9.3.3.7
Master Connection State bit in VACON
If the EtherNet/IP communication with the master device is functional, the bit 15 in the VACON
FBFixedControlWord is set to 1. If the communication with the master device is not working, the bit
15 in the FBFixedControlWord is set to 0.
9.3.4
Mapping of VACON
This section specifies how the VACON
Assemblies.
9.3.4.1
FBFixedStatusWord
For details on FBFixedStatusWord, see Chapter 11.3 "Vacon® Status Word - FBFixedStatusWord".
9.3.4.2
Ready Indication bit in VACON® FBFixedStatusWord
The "Ready Indication" bit 0 in the VACON
Input Assembly which supports this bit.
9
®
FBFixedControlWord
FBFixedControlWord is set to 1. Otherwise the bit is set to 0.
®
FBFixedControlWord
®
FBFixedControlWord
®
data onto Standard Input Assemblies
®
data is mapped onto the data in the Standard Input
®
FBFixedControlWord is set to 1. Otherwise the
®
FBFixedControlWord
®
FBFixedControlWord
®
FBFixedControlWord
®
FBFixedStatusWord is mapped to the "Ready" bit in an