EtherNet/IP
9.3.4.3
Run/Stop Indication bit in VACON® FBFixedStatusWord
The "Run/Stop Indication" bit 1 in the VACON
"Running2" bits in an Input Assembly which supports these bits. The state of the Running1 and
Running2 bits depends further on the "Direction Indication" bit 2 of the VACON
as follows:
Running1
Running2
9.3.4.4
Direction Indication bit in VACON® FBFixedStatusWord
See Chapter 9.3.4.3 "Run/Stop Indication bit in VACON® FBFixedStatusWord".
9.3.4.5
Fault Indication bit in VACON® FBFixedStatusWord
The "Fault Indication" bit 3 in the VACON
Input Assembly which supports this bit.
9.3.4.6
Alarm Indication bit in VACON® FBFixedStatusWord
The "Alarm Indication" bit 4 in the VACON
an Input Assembly which supports this bit.
9.3.4.7
Setpoint Reached Indication bit in VACON® FBFixedStatusWord
The "Setpoint Reached Indication" bit 5 in the VACON
"AtReference" bit in an Input Assembly which supports this bit.
9.3.4.8
Fieldbus Control indication in Input Assemblies
The selected control place is indicated in the Input Assemblies which contain the "CtrlFromNet" bit.
If the control place is assigned to fieldbus then this bit is set to 1, else it is 0.
9.3.4.9
Fieldbus Reference indication in Input Assemblies
The selected reference is indicated in Input Assemblies which contain the "RefFromNet" bit. If the
reference is assigned to fieldbus then this bit is set to 1, otherwise it is 0.
9.3.4.10
FBSpeedReference in percentage
This is the reference 1 to the AC drive. The allowed scaling is from 0 to 10000. In the application, the
value is scaled in percentage of the frequency area between set minimum and maximum frequency.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
®
FBFixedStatusWord is mapped to the "Running1" and
Table 200. Run/Stop Bit Indication Map
Run/Stop = 0
Direction = X
Direction = 0
0
0
®
FBFixedStatusWord is mapped to the "Faulted" bit in an
®
FBFixedStatusWord is mapped to the "Warning" bit in
®
®
FBFixedStatusWord
Run/Stop = 1
Direction = 1
1
0
0
1
FBFixedStatusWord is mapped to the
vacon • 199
9