System Redundancy

Redundancy is a requirement in process automation systems for high availability and reduced
production downtimes. PROFINET System Redundancy provides a solution to build a system with
redundant PN controllers, devices and communication.
PROFINET System Redundancy fulfills among others the following requirements:
• Highly reliable communication
• Short take over time
• Bumpless IO data during fault recovery
• Monitoring of the backup connection
System redundancy implements two redundant PN controllers, one working as primary and other
as backup. These controllers can be connected via a redundant network to PN devices. This is,
however, not mandatory as system redundancy has different levels which are independent from
each other, meaning that PN controller, Ethernet media and PN device can have different
redundancy configurations.
OPTEA supports "S2" level of System Redundancy as well as Media Redundancy Protocol (MRP) for
redundant connectivity.
S2 uses a single PROFINET interface (NAP = Network Access Point), and two SR-ARs (System
Redundancy Application Relations = connections), one to each PN controller. Redundant PN
controllers have parallel access to a SR PN device, but only one AR acts as a primary (SR-ARa) and
the other is backup (SR-ARb).
8
Primary
Redundant Network
Device with
redundant
connectivity
Figure 45. System Redundancy overview
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Backup
Device with
singular
connectivity
11957_uk
PROFINET IO

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the optea and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Opte9

Table of Contents

Save PDF