vacon • 92
7.6.3

Example 3 - Exception response

In an exception response, the Slave sets the most-significant bit (MSB) of the function code to 1. The
Slave returns an exception code in the data field.
Command Master - Slave:
ADDRESS
FUNCTION
DATA
ERROR CHECK
Message frame:
01
04
17
Exception response
Answer Slave - Master:
ADDRESS
FUNCTION
DATA
ERROR CHECK
Reply frame:
01
84
04
7
Starting address HI
Starting address LO
No. of registers HI
No. of registers LO
CRC HI
CRC LO
70
00
05
34
Error code
CRC HI
CRC LO
42
C3
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
01 hex
Slave address 1 hex (= 1)
04 hex
Function 4 hex (= 4)
17 hex
Starting address 1770 hex (= 6000)
70 hex
Invalid number of registers 0005 hex (=
00 hex
5)
05 hex
34 hex
66 hex
CRC 3466 hex (= 13414)
55
01 hex
Slave address 1 hex (= 1)
84 hex
Most significant bit set to 1
04 hex
Error code 04 => Slave device failure
42 hex
C3 hex
CRC 42C3 hex (= 17091)