Vacon optea Installation Manual page 106

Advanced/dual port ethernet board
Hide thumbs Also See for optea:
Table of Contents

Advertisement

vacon • 106
Bit 7: Fault acknowledge
This bit is used to acknowledge faults in the drive. When a rising edge (0 -> 1) is seen in this bit by
the option board, it requests the drive to acknowledge present faults. The functionality of this bit is
rising-edge sensitive only.
Bit 10: Control by PLC
This bit is used by the master to indicate that it is in control of the slave and that the commands sent
via fieldbus are valid.
During operation, this bit must be 1. If the drive is not operating and this bit is 0, the drive cannot be
started.
If the drive is operating, and this bit becomes 0, the option board freezes the process data provided
to the drive, and sets its state to FAULT. The drive reaction to this fieldbus fault depends on the drive
parameterization.
8.3.3.2
PROFIdrive Status Word 1 (ZSW1)
The table below lists the assignments of the status word 1.
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14-15
Bit 0: Readiness to switch on
This bit indicates whether the drive is ready to switch on the power electronics. When the bit has the
value 0, the drive is not ready to switch on the power electronics. When the bit has the value 1, the
drive is ready to switch on the power electronics.
Bit 1: Readiness to operate
This bit indicates whether the drive is ready to begin operation. When the bit has the value 0, the
power electronics is switched off and the drive is unable to begin operation. When the bit has the
value 1, the power electronics is switched on and the drive can begin operation if requested by the
master.
8
Table 67. Overview of the assignments of bits of the status word 1
Bit value is 1
Ready to Switch On
Ready To Operate
Operation Enabled (drive follows set-
point)
Fault Present
Coast Stop Not Activated (No OFF2)
Quick Stop Not Activated (No OFF3)
Switching On Inhibited
Warning Present
Speed Error Within Tolerance Range
Control by PLC Requested
f Or n Reached Or Exceeded
Device-specific
Drive running
Drive is ready
Device-specific
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Significance
Bit value is 0
Not Ready To Switch On
Not Ready To Operate
Operation Disabled
No Fault
Coast Stop Activated (OFF2)
Quick Stop Activated (OFF3)
Switching On Not Inhibited
No Warning
Speed Error Out Of Tolerance Range
No Control by PLC Requested
f Or n Not Reached
Device-specific
Drive stopped
Drive is not ready
Device-specific
PROFINET IO