Retrieve Input Status - Symmetricom SSU-2000 Technical Reference

Synchronization supply unit and synchronization distribution unit
Hide thumbs Also See for SSU-2000:
Table of Contents

Advertisement

Chapter 2 TL1 Reference

Retrieve Input Status

Retrieve Input Status
This command returns the condition (current operating mode and readings) of the
input ports.
Syntax
RTRV-STATUS-INPUT:[tid]:[aid]:ctag;
Parameter
[aid]
Response Format
One line is returned for each port designated by the aid.
^^^"aid:mstat,pstate,(pha),(phb),pql" <cr lf>
where:
= module or port access identifier
aid
= module status {OK | DIS | FLT}
mstat
= the port state {OK | DIS | FLT}
pstate
and
pha
phb
available
= current pql level (read or provisioned) being reported by the port, if
pql
available. If pql = 0 , then the pql is not applicable for that port.
Example
SSU_2000 06-03-08 20:28:19
M
100 COMPLD
"S1A03-01:OK,OK,(-29),(-8),2"
"S1A04-01:OK,OK,(-20),(-72),4"
"S1A05-01:OK,DIS,NA,NA,4"
;
74
SSU-2000 Technical Reference
Value
Retrieves the parameters from all Input modules in the
ALL
shelf.
Retrieves parameters from the specified Input module [or
S1Ay[-z]
port].
= current 1-second phase values in nanoseconds, or NA if not
Description
12713020-003-2 Revision F.01 – January 2007