Chapter 6 Alarms and Events
Communication Module Alarms and Events
Table 6-6. Basic +SNMPv2 and Basic +NTP + SNMPv2 Communications Module Alarm and Event Messages
Alarm/
Typical Alarm/Event/Trap
Event/
Response
Trap ID
000
Communication, Fault
001
InterCommunication, Fault
002
Power-A, Lost
003
Power-B, Lost
004
SPI Watchdog, Timeout
005
Shelf #2 Comm, Lost
006
Shelf #3 Comm, Lost
007
Shelf #4 Comm, Lost
008
Shelf #5 Comm, Lost
009
Detect Mdl Removed, Fault
105
KeepAlive, SSU2000
129
Install, Comm Module
130
Remove, Comm Module
131
Enable, Comm Module,
COML
132
Disable, Comm Module,
COML
133
Restart, in 5 seconds,
COML
144
Log In, JAY, COML, level: 2
145
Log Out, TIM, COML, level: 2
146
Auto Out, TIM, COML, level: 3
147
Msg, <HELLO BILL>, COML
148
Not Acknowledged, 1A01
150
Module Status, Fault, 1A04
298 SSU-2000 Technical Reference
Corrective Action
Unable to communicate with other modules. Re-seat modules.
Identifies master output controller. No action necessary.
Verify that the fuse for Power A is properly installed and not OPEN.
Verify that Power Bus A is providing –48 VDC to the unit. If no
power is connected to the Power A input and there is no plan to
connect power, issue the command
Verify that the fuse for Power B is properly installed and not
OPEN.
Verify that Power Bus B is providing –48 VDC to the unit. If no
power is connected to the Power B input and there is no plan to
connect power, enter the command AL 10-1 IG at the prompt.
Unable to communicate with other modules. Re-seat module.
Unable to communicate with Expansion Shelf 2. Check cables.
Unable to communicate with Expansion Shelf 3. Check cables.
Unable to communicate with Expansion Shelf 4. Check cables.
Unable to communicate with Expansion Shelf 5. Check cables.
A module has been removed from the system or is not responding
to Comms module queries. Replace the removed module with the
same type, or issue the command CONFIG xAy REMOVE to
remove the module information from the system database.
The Keep Alive function has been enabled/ disabled.
The Comms module has been installed.
The Comms module has been removed.
The Comms module has been enabled.
The Comms module has been disabled.
The Comms module has been rebooted (Warm boot).
User at indicated level has logged in.
User at indicated level has logged out.
System automatically logging out a user.
Message sent from a user.
Module configuration could not be obtained.
Module did not boot properly.
Description/
AL 10-1 IG
at the prompt.