Retrieve Frequency Data - Symmetricom SSU-2000 Technical Reference

Synchronization supply unit and synchronization distribution unit
Hide thumbs Also See for SSU-2000:
Table of Contents

Advertisement

Chapter 2 TL1 Reference

Retrieve Frequency Data

Retrieve Frequency Data
This command returns the current frequency measurements for the specified
input(s) on the DS1, E1, Sine, and GPS Input modules.
Syntax
RTRV-DATA-FREQ:[tid]:[aid]:ctag;
Parameter
[aid]
Response Format
^^^"aid:(freqa),(freqb)"<cr lf>
where:
= module or port access identifier
aid
= frequency of the port versus clock A
freqa
= frequency of the port versus clock B
freqb
Example
SSU_2000 06-06-26 13:38:57
M
100 COMPLD
"S1A03-01:(0),(0)"
"S1A03-02:(0),(0)"
"S1A03-03:(0),(0)"
"S1A04-01:(-3),(-31)"
"S1A05-01:(5),(-23)"
"S1A06-01:(0),(0)"
"S1A06-02:(0),(0)"
"S1A06-03:(0),(0)"
;
Related Commands
64
SSU-2000 Technical Reference
Value
Retrieves the current frequency measurements from all
ALL
modules that are currently active in the entire shelf.
Retrieves the current frequency measurements from the
S1Ay[-z]
specified module [or port].
Description
12713020-003-2 Revision F.01 – January 2007