Set Japan Sine Input Parameters
This command sets the parameters for the specified Japan Sine Input module or
ports. If
ALL
in the shelf.
Syntax
SET-PRMTR-INPSINE:[tid]:[aid]:ctag::[pstate],[pri],[pql],[frequency],
[csflt];
Parameter
aid
pstate
pri
pql
frequency
csflt
Related Commands
Retrieve Japan Sine Input
12713020-003-2 Revision F.01 – January 2007
is specified, then the command applied to all Japan Sine Input modules
Format
Sets the parameters for the specfied Japan Sine Input
S1Ay[-z]
module [or port].
Turns the specified module [or port] on or off.
ON | OFF
Sets the Priority for the specified module [or port]; MON =
1 - 10 |
Monitor.
MON
Sets the Priority Quality Level for the specified module [or
1 - 16
port].
Sets the frequency (in MHz) expected on the input.
1.544 |
6.312
Sets the external Cesium fault alarm input.
HI | LO
|OFF
Parameters, on page 78
Chapter 2 TL1 Reference
Set Japan Sine Input Parameters
Description
SSU-2000 Technical Reference 153