Table 6-10. DS1/E1 Input Module Alarm and Event Messages (Continued)
Alarm/
Typical Alarm/Event/Trap
Event/
Response
Trap ID
134
Cannot Enable, Input
Module, COML
144
Zero Phase, B, COML
145
Rcv Pql Chg, 3, old=4
146
Phase Buildout, 334000,
335000, Clk-B
193
DS1 Framer, ESF, COML
194
E1 Framer, CCS, COML
195
Freq, 10 MHz, COML
196
ZS, On, COML
197
SSM, Off, COML
198
CRC, On, COML
199
Port, Disable, COML
200
SSM, Auto, COML
201
Priority, 5, COML
202
SSM Bit, 4, COML
203
Prov PQL, 5, COML
204
MTIE Err Limit, T100, L1,
550, COML
205
Gain, On, COML
206
CSFlt, Off, COML
207
Err Cnt, BPV, 16, COML
208
Clr Cnt, OOF, 5, COML
209
Freq Err Limit, Clk-A, 100,
COML
210
Freq Clr Limit, Clk-A, 800,
COML
211
MTIE Clr Limit, T100, L1,
500, COML
212
MTIE Limit, DS1, COML,
Setting
213
PBO, Report, COML
214
Freq Tau, Clk-A, 400, COML
12713020-003-2 Revision F.01 – January 2007
Corrective Action
Internal firmware conflict. Restart module; if the problem persists,
call Symmetricom Global Services.
User has forced the phase to be cleared.
Input has received a different PQL.
Input performed phase buildout and difference in Phase that cause
PBO.
An Input framer setup change.
An Input framer setup change.
User changed input framer setup.
User changed input framer setup.
User changed input SSM capability.
User changed CRC setup.
User Enabled | Disabled input port.
User changed SSM setup.
User changed input priority level.
User changed SSM Bit location (E1 only).
User changed input provisioned PQL.
User changed input MTIE limits (L1 | L2).
User changed the input gain control.
User changed input Cesium Fault control.
Signal Alarm Error Count (LOS, AIS, OOF, BPV, or CRC).
Current Signal Alarm Clear Count (LOS, AIS, OOF, BPV, or CRC).
The frequency error limit settings have been changed.
The frequency clear limit settings have been changed.
The MTIE error limit settings have been changed.
The MTIE clear limit settings have been changed.
Phase Build-out system response has been changed to the
indicated setting.
The frequency TAU limits have been set.
Chapter 6 Alarms and Events