Verification Tables For Iparameter Settings In Ac500-S Safety I/Os - ABB AC500-S Safety User Manual

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
6.
Go to F-Parameter tab and press "Calculate" button once more, even if the previous value is still avail-
able. Compare that the value shown in "Checksum iParameter" field and the one in F_iPar_CRC field
of the F-Parameter editor are the same.
ð If F_iPar_CRC values are the same, then the verification procedure for given iParameter settings of
the given AC500-S Safety I/O module was successfully passed.
Important!
n
If any errors (F_iPar_CRC or iParameters are not equal) were identified during Steps 1 ... 6, then one
has to re-do the same procedure from the beginning. If after this second repetition there is still inconsis-
tency, contact ABB technical support for help.
n
Note, if iParameters values were verified as described in Steps 1 ... 6, you can reuse this iParameter
combination with the given F_iPar_CRC for further modules of the same type without repeating the verifi-
cation procedure described above.

6.5.2 Verification tables for iParameter settings in AC500-S Safety I/Os

The instructions below provide a basis for cross-check of values set for iParameters in "AI581-S", "DI581-S"
and "DX581-S" tabs.
30.03.2017
Checklists for AC500-S Commissioning
AC500-S
Safety I/Os
417