ABB AC500-S Safety User Manual page 326

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Typical Timing Diagram
Fig. 113: Timing diagram for SF_TestableSafetySensor
The following conditions force a transition to the Error state:
n
Test time overrun without delayed sensor feedback.
n
Test without sensor signal feedback.
n
Invalid static reset signal in the process.
n
Plausibility check of the monitoring time setting.
In the event of an error, the S_OSSD_Out output is set to FALSE and remains in this safe state.
Once the error has been removed and the sensor is on (S_OSSD_In = TRUE) – a reset removes the error
state and sets the S_OSSD_Out output to TRUE.