DX581-S digital safety input/output module > Technical data
Data
Number of channels per module (transistor outputs)
Terminals of reference potential for all outputs (minus pole of
the process supply voltage, signal name ZP)
Terminals of common power supply voltage for all outputs (plus
pole of the process supply voltage, signal name UP)
Output voltage for signal 1
Output delay (0 ➔ 1 or 1 ➔ 0)
Output current
Data
Rated value, per channel at UP = 24 V
Maximum value (all channels together)
Leakage current with signal 0
Short-circuit proof/overload proof
Overload message (channel passivation), I > 0.7 A
Output current limitation (automatic reactivation after short-cir-
cuit/overload)
Resistance to feedback against 24 V signals
Demagnetization by internal suppressor diods when switching
off inductive loads
Rated protection fuse on UP
Switching frequency
Data
With resistive load
With inductive loads
Cable length
Data
Max. cable length, shielded
Max. cable length, unshielded
134
AC500-S
Value Unit
8
1.9 ... 4.9
1.8 ... 4.8
UP – 3 V
on request
Value Unit
500 mA
4 A
< 0.5 mA
yes
yes
yes
yes
yes
4.5 A
on request
on request
Value Unit
1000 m
600 m