Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
Safety I/Os
6.5.2.3
DX581-S Safety I/O tables
Fig. 131: The "DX581-S Configuration" Tab is a readback view for iParameters set in "DX581-S" Tab.
1
"DX581-S" Tab
2
"DX581-S Configuration" Tab
1.
Compare that "Check supply" parameters have the same values "On" or "Off" (English settings) in both
"DX581-S" and "DX581-S Configuration" tabs.
2.
Refer to "DX581-S" tab and calculate "Input channel 0" decimal equivalent (Dec_InputChannel0) as:
Dec_InputChannel0 = Configuration_Value + Test_Pulse_Value + Input_Delay_Value
where
Configuration_Value:
0 ➔ Not used
1 ➔ 1 channel
2 ➔ 2 channel equivalent
3 ➔ 2 channel antivalent
Test_Pulse_Value:
0 ➔ Disabled
8 ➔ Enabled
Input_Delay_Value:
16 ➔ 1 ms
32 ➔ 2 ms
48 ➔ 5 ms
64 ➔ 10 ms
80 ➔ 15 ms