DANGER!
The average temperature (MTBF calculation base) for both the extended temperature range (–40 °C
... +70 °C) as well as for standard temperature range (0 °C ... +60 °C) is defined to +40 °C.
Ensure that average operating temperature for used AC500-S-XC modules does not exceed +40 °C.
Humidity
Data
Relative humidity with condensation (Operating/Storage)
Air pressure
Data
Operating air pressure
Operating altitude
Reduction of operating temperature at an air pressure of < 795
hPa (or > 2000 m above sea level)
Immunity to corrosive gases
Data
Operating: according to: ISA S71.04.1985 Harsh group A, G3/GX IEC 60721-3-3
3C2 / 3C3
Immunity to salt mist
Data
Operating: horizontal mounting only, according to: IEC 60068-2-52 severity level:
1
Electromagnectic Compatibility
Data
Radiated emission (radio disturbance) according to CISPR 16-2-3
Conducted emission (radio disturbance) according to CISPR 16-2-1, CISPR
16-1-2
Electrostatic discharge (ESD) according to IEC 61000-4-2, zone B, criterion B
Fast transient interference voltages (burst) according to IEC 61000-4-4, zone B,
criterion B
High energy transient interference voltages (surge) according to IEC 61000-4-5,
zone B, criterion B
Influence of radiated disturbances according to IEC 61000-4-3, zone B, criterion A
Influence of line-conducted interferences according to IEC 61000-4-6, zone B, cri-
terion A
30.03.2017
System data for AC500-S-XC
AC500-S
Value Unit
100 %
Value Unit
1080 ... 620 hPa
–1000 ... 4000 m
10 (e.g. 70 °C to
K
60 °C)
Value
yes
Value
yes
Value
yes
yes
yes
yes
yes
yes
yes
447