DANGER!
The input delay accuracy has to be calculated based on the following assumptions:
Not used for safety analog inputs;
If no test pulses are configured for the given digital safety input, then input delay accuracy can be
calculated as 1 % of set input delay value (however, input delay accuracy value must be at least
0.5 ms!)
If test pulses are configured for the given digital safety input, then depending on the type of the
module (DI581-S or DX581-S) and set input delay value, the following input delay accuracy values
can be used in SFRT calculations:
The following terms are defined in Fig. 126 and Fig. 127:
n
Device_WD1 is an internal input device watchdog time in ms which includes:
Input delay (variable as parameter; not used for safety analog inputs which have an internal input
delay of 67.5 ms in the worst case);
Input delay accuracy (see tables below)
Test pulse low phase (fixed to 1 ms and optional (only if test pulses are used); not used for safety
analog inputs);
Two times internal cycle time (fixed; AI581-S ➔ 4.5 ms, DX581-S ➔ 5.5 ms and DI581-S ➔ 6.5 ms);
n
F_WD_Time1 is the first watchdog time in ms for receipt of the new valid telegram (variable as parameter
and depends on system configuration);
n
F_Host_WD is the watchdog time in ms equal to three times of the set value using
SF_WDOG_TIME_SET POU (variable as parameter through SF_WDOG_TIME_SET POU and depends
on the number of F-Devices, safety application program and system configuration);
n
F_WD_Time2 is the second watchdog time in ms for receipt of the new valid telegram (variable as
parameter and depends on system configuration).
n
Device_WD2 is an internal output device watchdog time in ms which includes:
Internal safety output device cycle time (fixed; DX581-S ➔ 5.5 ms);
Output processing time (fixed to 1.5 ms);
Hardware delay (current dependent, e.g., ~1 ms (747 µs at 5 mA) and the maximum of 4 ms under
the maximum output current of 500 mA). If precise values are needed, please contact ABB technical
support.
Table 88: DI581-S safety module
Input delay (ms)
1
2
5
10
15
30
50
100
30.03.2017
Input delay accuracy (ms)
2
2
3
4
5
6
7
10
AC500-S
Safety times
Safety function response time