Allowed interruptions of power supply, according to EN 61131-2
Data
DC supply interruptions
Time between 2 DC supply interruptions, PS2
Environmental conditions
Data
Operating temperature*
Storage temperature
Transport temperature
Humidity without condensation
Operating air pressure
Storage air pressure
Operating altitude
Storage altitude
* Extended temperature ranges (below 0 °C and above +60 °C) can be supported in special versions of
Ä Appendix "System data for AC500-S-XC" on page 446)
SM560-S (
Creepage distances and clearances
The creepage distances and clearances meet the overvoltage category II, pollution degree 2.
Power supply units
For the supply of modules, power supply units according to PELV/SELV specifications must be used.
Electromagnetic compatibility
Ä TÜV Report [2]
30.03.2017
AC500-S
AC500-S Safety Modules
SM560-S Safety CPU > Technical data
Value Unit
< 10 ms
> 1 s
Value Unit
0 ... +60 °C
–40 ... +85 °C
–40 ... +85 °C
max. 95 %
> 800 hPa
> 660 hPa
< 2000 m above sea
level
< 3500 m above sea
level