ABB AC500-S Safety User Manual page 67

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

3.2.2.2
Transitions between Safety I/O module states
ID*
From
(1)
INIT
(2)
RUN (ok)
(3)
INIT
(4)
RUN (module
passivation)
(5)
INIT
(6)
SAFE STOP
(7)
RUN (ok)
(8)
RUN (channel
passivation &
reintegration)
(9)
RUN (ok)
(10)
RUN (ok)
(11)
RUN (ok)
(12)
RUN (channel
passivation &
reintegration)
(13)
RUN (module
passivation)
30.03.2017
Generic Safety I/O module behaviour > Safety I/O module states
To
Description
RUN (ok)
Safety I/O module comes to this state directly
after INIT during a normal start-up
INIT
Powering off/on
RUN (module
PROFIsafe watchdog, PROFIsafe communication
passivation)
error or undervoltage/overvoltage was detected
directly after INIT.
The Safety I/O module can reach this state also
after powering off/on the Safety I/O module if
Safety CPU with PROFIsafe F-Host continues
running and brings Safety I/O module to a fail-
safe RUN (module passivation) state after pow-
ering off/on
INIT
Powering off/on
SAFE STOP
Fatal error(s) (CPU test, RAM test, etc. failed)
took place
INIT
Powering off/on
RUN (channel
Channel error was identified by the Safety I/O
passivation and
module. The tests (whenever it is possible) are
reintegration)
continued for the given channel to be able to see
if the error is gone (e.g., wiring error was cor-
rected). As soon as the error is gone, the module
sets "Reintegration request" bit = "1" for the given
channel.
RUN (ok)
n
n
n
SAFE STOP
Fatal error(s) (CPU test, RAM test, etc. failed)
took place
RUN (module
PROFIsafe watchdog, PROFIsafe communication
passivation)
error or undervoltage/overvoltage was detected.
RUN (module
"activate_FV_C = 1" command was sent from the
passivation with
Safety CPU
a command)
SAFE STOP
Fatal error(s) (CPU test, RAM test, etc. failed)
took place
SAFE STOP
Fatal error(s) (CPU test, RAM test, etc. failed)
took place
AC500-S
AC500-S Safety Modules
The channel error is gone.
"Reintegration request" bit = 1 is set for the
given channel by the Safety I/O module.
"Acknowledge reintegration" bit (positive
edge) is set by PROFIsafe F-Host for the
given channel
67