Table 39: FB Name: SF_Antivalent
Name
Data Type
VAR_INPUT
Activate
BOOL
S_ChannelNC
BOOL
S_ChannelNO
BOOL
DiscrepancyTime
TIME
VAR_OUTPUT
Ready
BOOL
S_AntivalentOut
BOOL
Error
BOOL
DiagCode
WORD
Notes: "Antivalent" means that during normal operation, the two inputs are in opposite states at the same
time. This is sometimes called "complementary" or "non-equivalent".
30.03.2017
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Initial Value
Description, Parameter Values
FALSE
Ä Table 31 "General Input Parameters"
on page 266
FALSE
Variable. NC stands for Normally Closed.
Input for NC connection.
FALSE: NC contact open.
TRUE: NC contact closed.
TRUE
Variable. NO stands for Normally Open.
Input for NO connection.
FALSE: NO contact open
TRUE: NO contact closed
T#0ms
Constant.
Maximum monitoring time for discrepancy status
of both inputs.
FALSE
Ä Table 32 "General Output Parameters"
on page 267
FALSE
Safety related output
FALSE: Minimum of one input signal "not active"
or status change outside of monitoring time.
TRUE: Both inputs signals "active" and status
change within monitoring time.
Ä Table 32 "General Output Parameters"
FALSE
on page 267
Ä Table 32 "General Output Parameters"
16#0000
on page 267
AC500-S
Configuration and programming
275