ABB AC500-S Safety User Manual page 329

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

DiagCode
State Name
C010
Test Error 1
C020
Test Error 2
Table 65: FB-specific status codes (no error):
DiagCode
State Name
0000
Idle
8001
Init
30.03.2017
State Description and Output Setting
Test time elapsed in state 8020.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Test time elapsed in state 8030.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
State Description and Output Setting
The function block is not active (initial state).
Ready = FALSE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
An activation has been detected by the FB.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
AC500-S
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
329

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents